Specificatii
RELEU TERMIC,INTRERUPTOR
MAGNETO-TERMIC CU REGLAJ INTRE 10 - 16A, DISJUNCTOR
MOTOR,INTRERUPATOR PROTECTIE MOTOR 10-16 EATON
PRODUSUL ESTE NOU SI NEFOLOSIT ,IN AMBALAJ ORIGINAL,FARA DEFECTIUNI SAU LIPSURI.
DATE TEHNICE:
Part no. | PKZM0-16 | ||
Article no. | 046938 | ||
Catalog No. | XTPR016BC1NL | ||
121A138 | |||
Delivery programme | |||
Product range | PKZM0 motor protective circuit-breakers up to 32 A | ||
Basic function | Motor protection | ||
0000SPC-571 | |||
Notes | Also suitable for motors with efficiency class IE3. IE3-ready devices are identified by the logo on their packaging. |
||
Connection technique | Screw terminals | ||
Max. motor rating | |||
AC-3 | |||
220 V 230 V 240 V | P | kW | 4 |
380 V 400 V 415 V | P | kW | 7.5 |
440 V | P | kW | 9 |
500 V | P | kW | 9 |
660 V 690 V | P | kW | 12.5 |
Setting range | |||
Overload releases | Ir | A | 10 - 16 |
Short-circuit releases | |||
max. | Irm | A | 248 |
Notes | |||
Phase failure sensitivity to IEC/EN 60947-4-1, VDE 0660 part 102. | |||
can be snapped-on to IEC/EN 60715 top-hat rail with 7.5 or 15 mm height | |||
000Z412 PTB 10 ATEX 3013, observe Manual MN03402003Z-DE/EN |
|||
Technical data | |||
General | |||
Standards | IEC/EN 60947, VDE 0660 | ||
Climatic proofing | Damp heat, constant, to IEC 60068-2-78 Damp heat, cyclic, to IEC 60068-2-30 |
||
Ambient temperature | °C | ||
Storage | ϑ | °C | -40 - +80 |
Open | °C | - 25 - 55 | |
Enclosed | °C | - 25 - 40 | |
Mounting position | 1210DRW-68 | ||
Direction of incoming supply | as required | ||
Degree of protection | |||
Device | IP20 | ||
Terminations | IP00 | ||
Protection against direct contact | Finger and back-of-hand proof | ||
Mechanical shock resistance half-sinusoidal shock 10 ms to IEC 60068-2-27 | g | 25 | |
Altitude | m | 2000 | |
Terminal capacity screw terminals | mm2 | ||
Solid | mm2 | 1 x (1 - 6) 2 x (1 - 6) |
|
Flexible with ferrule to DIN 46228 | mm2 | 1 x (1 - 6) 2 x (1 - 6) |
|
Solid or stranded | AWG | 18 - 10 | |
Specified tightening torque for terminal screws | |||
Main cable | Nm | 1.7 | |
Control circuit cables | Nm | 1 | |
Main conducting paths | |||
Rated impulse withstand voltage | Uimp | V AC | 6000 |
Overvoltage category/pollution degree | III/3 | ||
Rated operational voltage | Ue | V AC | 690 |
Rated uninterrupted current = rated operational current | Iu = Ie | A | 32 or current setting of the overcurrent release |
Rated frequency | f | Hz | 40 - 60 |
Rated frequency | Hz | 40 - 60 | |
Current heat loss (3 pole at operating temperature) | W | 6 | |
Lifespan, mechanical | Operations | x 106 | 0.1 |
Lifespan, electrical (AC-3 at 400 V) | Operations | x 106 | 0.1 |
Maximum operating frequency | Ops./h | ||
Max. operating frequency | Ops/h | 40 | |
Short-circuit rating | |||
DC | |||
Short-circuit rating | kA | 60 | |
Short-circuit rating | 60 (up to PKZM0-16) 40 (PKZM0-20 to PKZM0-32) |
||
Motor switching capacity | kArms | ||
AC-3 (up to 690 V) | A | 32 | |
DC-5 (up to 250 V) | A | 25 (3 contacts in series) | |
Trip blocks | |||
Temperature compensation | |||
to IEC/EN 60947, VDE 0660 | °C | - 5…40 | |
Operating range | °C | - 25…55 | |
Temperature compensation residual error for T > 40 °C | ≦ 0.25 %/K | ||
Setting range of overload releases | x Iu | 0.6 - 1 | |
Short-circuit release fixed | x Iu | 15 | |
Fixed short-circuit release | Basic device 15.5 x Iu | ||
Short-circuit release tolerance | ± 20% | ||
Phase-failure sensitivity | IEC/EN 60947-1-1, VDE 0660 Part 102 | ||
Data for design verification according to IEC/EN 61439 | |||
Technical data for design verification | |||
Rated operational current for specified heat dissipation | In | A | 16 |
Equipment heat dissipation, current-dependent | Pvid | W | 6.43 |
Heat dissipation capacity | Pdiss | W | 0 |
IEC/EN 61439 design verification | |||
10.2 Strength of materials and parts | |||
10.2.2 Corrosion resistance | Meets the product standard's requirements. | ||
10.2.3.1 Verification of thermal stability of enclosures | Meets the product standard's requirements. | ||
10.2.3.2 Verification of resistance of insulating materials to normal heat | Meets the product standard's requirements. | ||
10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects | Meets the product standard's requirements. | ||
10.2.4 Resistance to ultra-violet (UV) radiation | Meets the product standard's requirements. | ||
10.2.5 Lifting | Does not apply, since the entire switchgear needs to be evaluated. | ||
10.2.6 Mechanical impact | Does not apply, since the entire switchgear needs to be evaluated. | ||
10.2.7 Inscriptions | Meets the product standard's requirements. | ||
10.3 Degree of protection of ASSEMBLIES | Does not apply, since the entire switchgear needs to be evaluated. | ||
10.4 Clearances and creepage distances | Meets the product standard's requirements. | ||
10.5 Protection against electric shock | Does not apply, since the entire switchgear needs to be evaluated. | ||
10.6 Incorporation of switching devices and components | Does not apply, since the entire switchgear needs to be evaluated. | ||
10.7 Internal electrical circuits and connections | Is the panel builder's responsibility. | ||
10.8 Connections for external conductors | Is the panel builder's responsibility. | ||
10.9 Insulation properties | |||
10.9.2 Power-frequency electric strength | Is the panel builder's responsibility. | ||
10.9.3 Impulse withstand voltage | Is the panel builder's responsibility. | ||
10.9.4 Testing of enclosures made of insulating material | Is the panel builder's responsibility. | ||
10.10 Temperature rise | The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. | ||
10.11 Short-circuit rating | Is the panel builder's responsibility. The specifications for the switchgear must be observed. | ||
10.12 Electromagnetic compatibility | Is the panel builder's responsibility. The specifications for the switchgear must be observed. | ||
10.13 Mechanical function | The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. | ||
Technical data ETIM 5.0 | |||
Low-voltage industrial components (EG000017) / Motor protective circuit-breaker (EC000074) | |||
Electric engineering, automation, process control engineering / Low-voltage switch technology / Circuit breaker (LV < 1 kV) / Circuit breaker motor protection (ecl@ss8-27-37-04-01 [AGZ529012]) | |||
Setting range overload protector | A | 10 - 16 | |
Adjustment range undelayed short-circuit release | A | 248 - 248 | |
Phase failure sensitive | Yes | ||
Switch off technique | Thermomagnetic | ||
Rated operating voltage | V | 690 - 690 | |
Rated permanent current Iu | A | 16 | |
Rated operation power at AC-3, 230 V | kW | 4 | |
Rated operation power at AC-3, 400 V | kW | 7.5 | |
Connection type main current circuit | Screw connection | ||
Device construction | Built-in device fixed built-in technique | ||
With integrated auxiliary switch | No | ||
With integrated under voltage release | No | ||
Number of poles | 3 | ||
Rated short-circuit breaking capacity lcu at 400 V, AC | kA | 50 | |
Degree of protection (IP) | IP20 | ||
Approvals | |||
Product Standards | UL 508; CSA-C22.2 No. 14; IEC60947-4-1; CE marking | ||
UL File No. | E36332 | ||
UL Category Control No. | NLRV | ||
CSA File No. | 165628 | ||
CSA Class No. | 3211-05 | ||
North America Certification | UL listed, CSA certified | ||
Specially designed for North America | No | ||
Suitable for | Branch circuit: Manual type E if used with terminal, or suitable for group installations | ||
Characteristics | |||
1210DIA-62 | |||
Motor-protective circuit-breaker tripping characteristic (high-capacity) compact starter, PKZM0-…T (not for PKM0-…), PKZM01 | |||
121U017 | |||
Let-through current | |||
121U016 | |||
Let-through energy | |||
Dimensions | |||
121X001 | |||
Motor-protective circuit-breaker with standard auxiliary
contact PKZM0-…(+NHI-E-…-PKZ0) PKZM0-…-T(+NHI-E-…-PKZ0) PKM0-…(+NHI-E-…-PKZ0) |
|||
121X002 | |||
Motor-protective circuit-breakers with lockable rotary
handles PKZM0-…+AK-PKZ0 |
|||
121X042 | |||
Motor-protective circuit-breakers with early-make auxiliary
contacts PKZM0-…+VHI-…-PKZ0 |
1.Ca urmare a
unor neplaceri avute in trecut, pentru cei sub 10 calificative
pozitive sau cei cu calificative negative acordate pentru
neridicare de colet,imi rezerv dreptul sa cer plata partial sau
integral in avans.Coletul va fi trimis abia dupa sosirea
banilor!
2.Negocierile,ofertele de pret se fac inainte de licitatie si nu dupa.Odata ce ati licitat inseamna ca ati acceptat automat pretul de listare si cheltuielile de transport.
3.In principiu nu sunt interesat de schimburi de niciun fel dar analizez orice oferta decenta in limita bunului simt.Desigur nu inseamna ca o si accept.
4.Daca aveti intrebari,oferte de pret sau doriti sa cereti detalii folositi forumul.
Imi rezerv
dreptul sa vand produsele si pe alte site-uri ca atare pentru a nu
avea neplaceri si discutii inutile va recomand sa intrebati
de disponibilitaea produsului inainte sa licitati.
Cel putin odata pe
zi incerc sa raspund la intrebari.
5.Dupa incheierea oricarei tranzactii se acorda calificative asigurandu-se astfel o transparenta in seriozitatea userilor.
6.Licitatiile de pe acest site sunt toate comisionate de catre administratia Okazii.ro, ca atare pentru licitatii false sau neridicare de colet se acorda automat (fara doar si poate!) calificativ negativ iar acumularea mai multor calificative negative atrage dupa sine excluderea de pe acest site.
7.Cumparatorul va confirma in scris prin e-mail sau SMS in cel mult 3 zile de la licitatie adresa de livrare completa si corecta.
8.Prefer livrare cu plata ramburs prin Posta Romana in 2-4 zile lucratoare sau livrare personala.Daca se doreste expedierea prin servicii de curierat ,contravaloarea produsului se va achita in avans in cont bancar iar cheltuielile de transport se vor plati curierului la livrare.
Coletul va pleca doar dupa intrarea banilor in cont!
Atentie! Nu trimit POST RESTANT!
Exclus expediere
prin Fan Courier!
9.Sunt persoana fizica si nu pot emite factura!
10.Daca nu sunteti de acord cu regulile mentionate anterior, va rog sa nu licitati!
Va multumesc pentru intelegere si va doresc mult succes pe Okazii.ro!
Modalitati de livrare si plata
LIVRARE
In Tasnad
-
- Predare personala in max. 3 zile lucratoare
PLATA
- - La predare
- - Ramburs
Politica de retur
- - Produsul nu se poate returna.